The rectangular structure of the high and low voltage coils is not as uniform as the conventional circular coil structure, but the high voltage coil is an epoxy resin cast rigid body structure sufficient to withstand the weight of the core and the axial electric power generated when the short circuit occurs. The low-pressure foil coil is less rigid than the resin. The radial electric power that shrinks inward when subjected to short-circuit is the harsh point of the amorphous alloy dry-type transformer when it is short-circuited, but after adjusting the length and length of the rectangular coil and the low-voltage coil and iron Special treatments such as laminating wood support pads between cores can meet the requirements of use.
SC(B)H15-M-30~1600/10 Series Resin Insulation Amorphous Metal Dry-type Power Transformer | |||||||||
Rated Capacity (KVA) |
Voltage Combination |
Connection Method |
Loss | No Load Current(%) |
Impendence Voltage(%) |
Weight (Kg) |
Dimension (mm) (L×W×H) |
||
HV(KV) | LV(KV) | No Load | Load(120℃) | ||||||
100 | 11 10.5 10 6.3 6 |
0.4 | Dyn11 | 130 | 1570 | 1.2 | 4 | 890 | 950×600×960 |
160 | 170 | 2130 | 1.1 | 1170 | 1220×600×1060 | ||||
200 | 200 | 2530 | 1.0 | 1400 | 1270×710×1160 | ||||
250 | 230 | 2760 | 1.0 | 1560 | 1350×760×1240 | ||||
315 | 280 | 3470 | 0.9 | 1770 | 1370×870×1360 | ||||
400 | 310 | 3990 | 0.8 | 2180 | 1460×870×1360 | ||||
500 | 360 | 4880 | 0.8 | 2440 | 1490×870×1430 | ||||
630 | 420 | 5880 | 0.7 | 2850 | 1760×1120×1490 | ||||
630 | 410 | 5960 | 0.7 | 6 | 3015 | 1710×970×1450 | |||
800 | 480 | 6960 | 0.7 | 3430 | 1850×1120×1600 | ||||
1000 | 550 | 8130 | 0.6 | 4050 | 1900×1120×1170 | ||||
1250 | 650 | 9690 | 0.6 | 4690 | 2030×1120×1880 | ||||
1600 | 760 | 11730 | 0.6 | 5610 | 2120×1120×1970 | ||||
2000 | 1000 | 14450 | 0.5 | 5820 | 2120×1120×1990 | ||||
2500 | 1200 | 17170 | 0.5 | 6730 | 2190×1120×2110 |
ZTELEC SC (B) H15 amorphous alloy dry power transformer with high safety performance and low loss.