Medium voltage dry type transformers have moved far beyond their early role as a niche indoor solution. Today they power hospitals, data centers, metro systems, wind farms, high-rise buildings and industrial plants where safety, cleanliness and low maintenance matter most.
For voltage classes up to 36kV, a modern Dry-type transformer can match many oil-filled designs in reliability while removing the fire and leakage risks that come with liquid insulation. This guide explains how these units work, what to specify and how to choose the right one.

What Are Medium Voltage Dry Type Transformers?
A medium voltage dry type transformer uses air or solid insulation instead of mineral oil. The windings are not immersed in liquid, so there is no oil to leak, ignite or require sampling.
In the medium voltage range, the primary voltage usually covers 6kV, 10kV, 11kV, 13.8kV, 20kV, 22kV, 24kV, 33kV and up to 36kV. Secondary voltages are typically 400V, 415V, 480V, 690V or another medium voltage level, depending on the network.
Capacities commonly range from about 100kVA to 20MVA, although most projects fall between 500kVA and 5000kVA.
Cast-Resin Transformer Technology Explained
How the Windings Are Built
A cast-resin transformer encapsulates its high-voltage windings in epoxy resin under vacuum. The process removes air bubbles and creates a solid, void-free insulation system with excellent dielectric strength.
Many designs add glass fiber or other fillers to improve mechanical strength and thermal performance. The result is a winding that resists cracking, moisture and contamination.
Why Vacuum Casting Matters
Partial discharge is a major cause of insulation aging in medium voltage equipment. Vacuum casting reduces trapped air, which helps keep partial discharge at very low levels.
Quality manufacturers test each unit and can provide partial discharge values in the routine test report. This is one of the best indicators of build quality.
Cast Resin vs VPI Designs
Vacuum pressure impregnated units are also dry type, but their coils are coated rather than fully encapsulated. They work well at lower voltages and in clean indoor rooms.
As voltage rises toward 36kV, fully cast designs are generally preferred for their stronger insulation, better humidity resistance and longer service life.
Key Advantages of Dry-Type Designs
Fire Safety
Epoxy resin and air insulation have a low fire load and are usually self-extinguishing. Many cast resin products meet F1 fire behavior classes, which is important for buildings with strict fire regulations.
This means fewer requirements for fire walls, oil pits and extinguishing systems, which can lower civil construction cost.
Environmental Protection
With no oil, there is no soil or water contamination risk. This makes dry type units attractive for green building projects, water treatment plants and environmentally sensitive sites.
Low Maintenance
There is no oil testing, filtering or topping up. Routine care is limited to cleaning dust, checking connections and inspecting temperature controllers.
Installation Flexibility
Because fire risk is low, these transformers can be installed close to the load, in basements, on upper floors or inside substations. Shorter low-voltage cable runs reduce losses and voltage drop.
Typical Applications up to 36kV
Commercial and Public Buildings
Hospitals, airports, shopping malls, hotels and office towers rely on dry type units for safe indoor power distribution. Quiet operation and low fire risk are major selling points.
Industrial Plants
Factories use them for motor loads, process lines and variable frequency drives. Special designs can handle harmonics and heavy cyclic duty.
Renewable Energy
Wind turbines often use dry type transformers inside the tower or nacelle because oil leakage is undesirable at height. Solar plants and energy storage systems also use them where compact, safe equipment is required.
Rail and Infrastructure
Metro stations, tunnels and railway systems value their fire performance and vibration resistance. Marine and offshore applications use special versions with corrosion protection.

Important Technical Specifications
Rated Power and Voltage
Define the rated kVA, primary voltage, secondary voltage and frequency. Also specify tap changer range, such as plus or minus 2 x 2.5%, to match grid variations.
Insulation Class and Temperature Rise
Common insulation systems are Class F with a temperature rise of 100K, or Class H with 125K. A transformer designed with a lower temperature rise runs cooler and generally lasts longer.
Basic Insulation Level
The lightning impulse and power frequency withstand levels must suit your system voltage. For a 36kV class unit, the insulation level is much higher than for a 12kV unit, so check these values carefully.
Impedance and Vector Group
Impedance usually falls between 6% and 8% for larger medium voltage designs. A higher value limits short-circuit current, while a lower value reduces voltage drop.
Dyn11 is the most common vector group for distribution, but Dyn5, Yyn0 and other options are available.
Losses and Efficiency
Ask for no-load loss and load loss at the reference temperature. Because the transformer is energized all year, lower no-load loss can create meaningful savings.
Many buyers now request low-loss designs with amorphous or high-grade silicon steel cores to meet energy efficiency rules.
Cooling and Protection
Natural Air Cooling
Most units use AN cooling, where air circulates naturally around the windings. It is simple, quiet and reliable.
Forced Air Cooling
Fans can raise the continuous capacity by about 30% to 40%. They are useful for peak loads, but they should not replace correct sizing.
Enclosures and IP Rating
Typical enclosures are IP20 for clean indoor rooms, IP21 or IP23 for light protection, and IP54 for harsher locations. If the transformer is near coastal air, dust or humidity, choose a higher protection class and corrosion-resistant finish.
Temperature Monitoring
PT100 sensors or PTC thermistors monitor winding temperature and trigger alarms or trips. A good temperature controller protects the transformer from overheating.
Standards and Testing
Look for compliance with IEC 60076-11, which covers dry type transformers. Depending on the market, you may also see IEEE C57.12.01, GB/T 10228 or EN 50588 for efficiency requirements.
Routine tests should include winding resistance, ratio, vector group, no-load loss, load loss, short-circuit impedance, applied voltage and induced voltage tests. Partial discharge measurement is strongly recommended for any cast-resin transformer above 12kV.
For higher confidence, request type test reports covering temperature rise, lightning impulse, climatic class, environmental class and fire behavior. These show that the design, not just the individual unit, has been verified.
Climatic, Environmental and Fire Classes
The E and C classes are often overlooked. The environmental class, such as E2, shows resistance to condensation and pollution. The climatic class, such as C2, shows suitability for low temperature operation and transport.
The fire class, such as F1, shows tested fire behavior. If the transformer will be installed in public buildings or tunnels, confirm these classes in the datasheet.
Dry Type vs Oil-Immersed Transformers
Oil-immersed transformers still have the upper hand in very high capacities, outdoor installations and initial purchase price. They also offer strong overload tolerance and are common in utility networks.
However, a dry type design wins when safety, indoor installation, maintenance reduction and environmental protection are priorities. When you include civil work, fire protection and maintenance, the total cost gap often becomes smaller than expected.
How to Choose the Right Transformer
Step 1: Define the Load
Calculate expected demand, peak load, harmonic content and future growth. Aim for a normal load of around 60% to 80% of the rating.
Step 2: Confirm the Voltage System
Check the grid voltage, tolerance, short-circuit level and neutral grounding method. These details affect insulation, impedance and protection design.
Step 3: Review the Site
Measure room size, ventilation, ambient temperature, humidity and altitude. Above 1000 meters, derating or a special design may be required.
Step 4: Compare Total Cost
Do not look only at purchase price. Consider energy losses, cooling needs, maintenance and expected lifespan.
Step 5: Evaluate the Manufacturer
Choose a supplier with in-house vacuum casting equipment, test facilities and experience in your voltage class. Ask for references and sample test reports.
Installation and Maintenance Tips
Allow enough clearance for airflow and safe access. Keep the room clean, dry and well ventilated, and avoid blocking air inlets.
Inspect terminals and bolted joints regularly, because loose connections create heat. Vacuum or blow off dust from the winding ducts at least once a year, and more often in dusty environments.
If the transformer has been stored or de-energized in a humid place, check insulation resistance before energizing it.
Common Buying Mistakes
A common error is selecting a transformer by kVA alone without checking harmonics or ambient temperature. Another is ignoring partial discharge values, which are a key quality indicator.
Some buyers also forget to specify the enclosure rating, cable entry or protective devices. Clear specifications at the inquiry stage prevent costly changes later.
Medium voltage dry type transformers up to 36kV offer a safe, clean and dependable solution for modern power systems. A properly specified Dry-type transformer reduces fire risk, simplifies maintenance and supports sustainable design goals.
When fire safety, moisture resistance and long service life matter, a vacuum-cast cast-resin transformer is often the best choice. Share your voltage, capacity, site conditions and standards with an experienced manufacturer to receive a solution tailored to your project.