Amorphous alloy transformer uses amorphous alloy as core, in which the metal atoms inside are arranged in disordered non-crystal sequence.It has lower loss than silicon steel materials, thus resulting in high effciency and energy saving.The area of hysteresis loop in amorphous alloy is far less than that in cold-rolled steel, therefore the loss of iron core is quite low, approximately 70% lower than traditional silicon steel lamination cores, making it be the ideal low-loss energy-saving transformer at present. Due to above features, amorphous alloy transformer has the advantages of less heat, low temperature rise, and stable running performance.


Parameter
 
SC(B)H15-M-30~1600/10 Series Resin Insulation Amorphous Metal Dry-type Power Transformer
Rated Capacity
(KVA)
HV(KV) LV(KV) Connection
Method
No Load Load(120℃) No Load
Current(%)
Impendence 
Voltage(%)
Weight  
 (Kg)
Dimension(mm)
 (L×W×H)
100 11 0.4 Dyn11 130 1570 1.2 4 890 950×600×960
160   170 2130 1.1 1170 1220×600×1060
200 10.5 200 2530 1.0  1400 1270×710×1160
250   230 2760 1.0  1560 1350×760×1240
315 10 280 3470 0.9 1770 1370×870×1360
400   310 3990 0.8 2180 1460×870×1360
500 6.3 360 4880 0.8 2440 1490×870×1430
630   420 5880 0.7 2850 1760×1120×1490
630 6 410 5960 0.7 6 3015 1710×970×1450
800   480 6960 0.7 3430 1850×1120×1600
1000   550 8130 0.6 4050 1900×1120×1170
1250   650 9690 0.6 4690 2030×1120×1880
1600   760 11730 0.6 5610 2120×1120×1970
2000   1000 14450 0.5 5820 2120×1120×1990 
2500   1200 17170 0.5 6730 2190×1120×2110